Thursday, October 31, 2024
Useful Resources for Brilliant Manufacturing, Operational & Industrial Intelligence Technology Enthusiasts!

Automation, Control & Plant Intelligence - Articles, Analysis, Reviews, Interviews & Views

OPC - OLE (Object Linking and Embedding) for Process Control :: The Industrial Interoperability Standard

Datablock or Poll Record
Knowledge Base

Automation Media's recommended most important key terminologies you need to know if you work in Automation, Controls, Brilliant Manufacturing, Operational & Industrial Intelligence or IoT etc. ; regardless of any vendor(s) you are dealing (Allen Bradley, GE Fanuc, Siemens, Modicon, Mitsubishi, Omron, Automation Direct etc).

  • This explanation may slighltly vary based on vendor/manufacturer.


  • Typically, poll record is old driver term for the specific data you want to access in a device. OPC Servers use the term datablock to refer to the same data because typically you want to access entire sections or blocks of data at one time.


  • You can define the data you want to access by entering the range of memory addresses the device uses to store the data and the type of data you want to read, (for example, Integer, ASCII, or Float). The driver needs the data type so that it can store the information correctly for your Human-Machine Interface (HMI)/SCADA software.


  • The driver also needs two time values:
  • How frequently to read data (called the poll rate).

  • How long the driver reads the data from the device and updates the poll record/datablock when there has been no request for it from your HMI software (called the access time).


  • Example:

    Suppose you want to read eight integer values from an Allen-Bradley device.
    The device stores these values starting with address N7:4.

    You want to read the data every 5 seconds and update the poll record/datablock for 15 seconds after requests have stopped.

    Using this information, you would specify the following for your poll record/datablock:

    Start address: N7:4
    End address: N7:11
    Data type: integer
    Poll rate: 5 seconds
    Access time: 15 seconds

    The poll record/datablock reads the following location in the device:

    00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20
    IIIII IIIII IIIII IIIII IIIII IIIIII IIIII IIIII



    Free OPC Clients   /   Free OPC Servers   /   Free OPC Utilities


    OPC Foundation owns all OPC trademarks including the OPC logo used throughout this site. Most of information in OPC Knowledge Base is from OPC foundation.
    Free Automation Stuff This information made available on Automation Media, are provided "as is" without any representation or warranty, express or implied, of any kind, including, but not limited to, warranties of merchantability, noninfringement, or fitness for any particular purpose. Automation Meida makes no warranty or representation regarding, and does not endorse, any linked Web sites or the information appearing thereon or any of the products or services described thereon.